New and well-forgotten old refrigerants. Refrigerants are compared thermodynamically in a model refrigeration cycle: liquid refrigerant boils at constant pressure p1p_1 and temperature T1T_1 (absorbing heat QQ), the vapour is compressed reversibly and adiabatically to T2T_2 (work WW), then cooled at constant pressure p2p_2 and returned to the initial state. For 1 mole of refrigerant with T1=280T_1 = 280 K and T2=380T_2 = 380 K, ideal vapour, the data are: NHX3\ce{NH3} — ΔHvap=21.3\Delta H_{vap} = 21.3 kJ mol−1^{-1}, CV(gas)=26.7C_V(\text{gas}) = 26.7 J K−1^{-1} mol−1^{-1}; CHFX2Cl\ce{CHF2Cl} — 20.020.0 kJ mol−1^{-1} and 48.848.8 J K−1^{-1} mol−1^{-1}; CFX3CHX2F\ce{CF3CH2F} — 22.122.1 kJ mol−1^{-1} and 7979 J K−1^{-1} mol−1^{-1}; CFX3CF=CHX2\ce{CF3CF=CH2} — 19.119.1 kJ mol−1^{-1} and 120120 J K−1^{-1} mol−1^{-1}. (a) Calculate QQ and WW for NHX3\ce{NH3} and CHFX2Cl\ce{CHF2Cl}. (b) The coefficient of performance is COP=Q/WCOP = Q/W; calculate it for both refrigerants. (c) Calculate the COP for CFX3CHX2F\ce{CF3CH2F} and CFX3CF=CHX2\ce{CF3CF=CH2} — did efficiency improve relative to CHFX2Cl\ce{CHF2Cl}?
Step 1 of 4: Heat absorbed during evaporation
Q=ν ΔHvap:Q(NHX3)=21.3 kJ,Q(CHFX2Cl)=20.0 kJQ = \nu\,\Delta H_{vap}: \quad Q(\ce{NH3}) = 21.3\ \text{kJ},\quad Q(\ce{CHF2Cl}) = 20.0\ \text{kJ}
Analysis

The heat taken up while 1 mol of liquid boils completely at T1T_1 equals the molar enthalpy of vaporization: Q(NHX3)=21.3Q(\ce{NH3}) = 21.3 kJ and Q(CHFX2Cl)=20.0Q(\ce{CHF2Cl}) = 20.0 kJ.