Problem 1
New and well-forgotten old refrigerants. Refrigerants are compared thermodynamically in a model refrigeration cycle: liquid refrigerant boils at constant pressure and temperature (absorbing heat ), the vapour is compressed reversibly and adiabatically to (work ), then cooled at constant pressure and returned to the initial state. For 1 mole of refrigerant with K and K, ideal vapour, the data are: — kJ mol, J K mol; — kJ mol and J K mol; — kJ mol and J K mol; — kJ mol and J K mol. (a) Calculate and for and . (b) The coefficient of performance is ; calculate it for both refrigerants. (c) Calculate the COP for and — did efficiency improve relative to ?
Step 4 of 4: COP of third- and fourth-generation refrigerants
Analysis
The same calculation gives for and for — both below 4.10, so the newer generations did not improve energy efficiency versus ; they were adopted for environmental (ozone, greenhouse) reasons instead.
Common pitfall. Use in J K mol and convert to kJ: forgetting the factor inflates by 1000 and destroys the COP.